Dass-055 C [updated]
| Symptom | Possible Cause | Corrective Action | | :--- | :--- | :--- | | No 4-20 mA output | Loop power missing or polarity reversed | Check voltage on Pin 1 and Pin 3. Ensure loop is closed. | | Output stuck at 4 mA | Pressure below zero or sensor diaphragm damaged | Isolate sensor and test with a dead-weight tester. Replace if diaphragm is ruptured. | | Discrete output oscillates | Hysteresis set too narrow | Reconfigure using the IO-Link interface (rev 1.1) to widen hysteresis by 2-5% of range. | | Temperature reading drifts (if equipped) | Adhesive thermal compound degraded | Reapply thermal paste to the sensor base. |